Title 13 PUBLIC SERVICES
Chapter 13.24 CROSS-CONNECTION CONTROL PLAN
13.24.040 Backflow prevention assemblies.
A. Approved Backflow Prevention Assemblies.
1. Only backflow prevention assemblies which are listed on
the "List of Approved Backflow Prevention Assemblies" published by the
Foundation for Cross-Connection Control and Hydraulic Research, University of
Southern California, shall be acceptable for installation by a water user
connected to the city of Columbia Falls water department potable
supply.
2. Upon request, the city of Columbia Falls water department
will provide a list of approved backflow prevention assemblies to any interested
person.
B. Existing Backflow Prevention Assemblies. Approved
backflow prevention assemblies that are currently in service shall be tested and
if found to be in serviceable condition can be left in service after certain
information (make, model, size, serial number, and test results) has been
provided to the city of Columbia Falls water department. The assembly must then
be tested yearly by a certified backflow prevention assembly tester (see Section
13.24.080) or more frequently if determined necessary by the city of Columbia
Falls water department. Existing backflow prevention assemblies found to be
unserviceable or whose application has been misapplied shall be removed and
replaced with an appropriate assembly approved by the city of Columbia Falls
water department.
C. Backflow Prevention Assembly Installation. Backflow
prevention assemblies shall be installed in a manner prescribed by the city of
Columbia Falls water department. Location of the assemblies should be as close
as practical to the user’s connection. The city of Columbia Falls water
department shall have the final authority in determining the required location
of a backflow prevention assembly.
1. Air-gap separation (AG). The air gap separation shall be
located on the user’s side of and as close to the service connection as is
practical. All piping from the service connection to the receiving tank shall be
above grade and be entirely visible. No water use shall be provided from any
point between the service connection and the air-gap separation. The water
inlet piping shall terminate a distance of at least two pipe diameters above the
supply inlet, but in no case less than one inch above the overflow rim of the
receiving vessel. Properly installed, the air gap may be used to protect
against all levels of backflow hazards.
2. Reduced pressure zone backflow prevention assembly (RP).
The approved reduced pressure zone backflow prevention assembly shall be
installed on the user’s side and as close to the service connection as is
practical. The assembly shall be installed a minimum of twelve inches above
grade and not more than thirty inches above grade measured from the bottom of
the assembly and with a minimum of twelve inches side clearance. The assembly
shall be installed in a horizontal position and be readily accessible for
maintenance and testing. Water supplied from any point between the service
connection and the RP assembly shall be protected in a manner approved by the
city of Columbia Falls water department. The water user must provide adequate
drainage to prevent flooding in the event the RP assembly bypasses water to
atmosphere and sufficient protection to prevent the assembly from freezing.
Properly installed, the RP may be used to protect against all levels of hazard
under both backpressure and backsiphonage conditions.
3. Double check valve assembly (DCA). The approved double
check valve assembly shall be located as close as practical to the user’s
connection and shall be installed above grade, if possible, and in a manner
where it is readily accessible for testing and maintenance. If a double check
valve assembly is put below grade, it must be installed in a vault such that
there is a minimum of six inches between the bottom of the vault and bottom of
the assembly and so that the top of the assembly is no more than a maximum of
eight inches below grade. Also, there must be a minimum of twenty-four inches
of clearance between the side of the assembly with the test cocks and side of
the vault, and also a minimum of twelve inches clearance between the other side
of the assembly and side of the vault. Special consideration must be given to
double check valve assemblies of the "Y" type. These assemblies must be
installed on their "sides" with the test cocks in a vertical position so that
either check valve may be removed for service without removing the assembly.
Vaults which do have an integrated bottom must be placed on a three inch layer
of gravel. The water user must provide adequate drainage to prevent flooding in
the event the assembly leaks or to accommodate spillage during testing and
repairs. The water user is responsible for providing adequate protection to
prevent freezing of the assembly. The DCA may be used to protect against a
non-health hazard under both backpressure and backsiphonage
conditions.
4. Pressure Vacuum Breaker (PVB). The approved pressure
vacuum breaker assembly shall be located as close as practical to the
user’s connection or meter and shall be installed at least twelve inches
above all downstream plumbing and the highest fixture flood level rim, outlet,
or highest point of water use. In no case should the PVB assembly be used if
backpressure could develop in the downstream piping. The PVB shall be installed
inline in a vertical position with adequate space to facilitate maintenance and
testing. The PVB shall be installed in an area where water spillage through the
vacuum relief valve (air inlet) is not objectionable. Adequate drainage to
floor drains should be provided to accommodate this spillage. The PVB shall not
be installed in a vent hood or where toxic or objectionable fumes or substances
could enter and contaminate the potable water piping. Prior to installation,
refer to the manufacturer’s literature concerning temperature ranges. The
PVB must be protected from freezing temperatures and if installed where
temperatures will reach one hundred twenty degrees Fahrenheit or forty-three
degrees Celsius or above, the hot water type of assembly must be used. Properly
installed, the PVB may be used to protect all levels of hazard under
backsiphonage conditions only.
5. Atmospheric Vacuum Breaker (AVB). The approved vacuum
breaker assembly shall be located as close as practical to the user’s
connection or meter and shall be installed at least six inches above all
downstream piping and the highest fixture flood level rim, outlet or highest
point of water use. In no case should the AVB assembly be used if backpressure
could develop in the downstream piping. The AVB shall be installed inline in a
vertical position with adequate space to facilitate maintenance and testing.
The AVB shall be installed in an area where water spillage through the vacuum
relief valve (air inlet) is not objectionable. Adequate drainage to the floor
drain must be provided to accommodate this spillage. The AVB shall not be
installed in a vent hood or where toxic or objectionable fumes or substances
could enter and contaminate the potable water piping. The AVB shall not be
installed where it will be in continuous operation or under continuous pressure
for more than twelve consecutive hours. When used for long periods of time the
air inlet valve could become stuck in the closed position. The AVB shall not
have any valves installed downstream from the assembly (the discharge side of
the plumbing should be exposed to the atmosphere). Prior to installation, refer
to the manufacturer’s literature for temperature ranges. The AVB must be
protected from freezing temperatures and if installed where temperatures will
reach one hundred ten degrees Fahrenheit or forty-three degrees Celsius or
above, the hot water type of assembly must be used. Properly installed, the AVB
can be used to protect against all levels of hazard under backsiphonage
conditions only.
D. Backflow Prevention Assembly Testing and
Maintenance.
1. The owners of any premises on which, or on account of
which, backflow prevention assemblies are installed, shall have the assemblies
tested by a person who holds a current certificate from any state certification
program authorizing the person to test backflow prevention assemblies or who
holds a current certificate from the American Society of Sanitary Engineers,
American Backflow Prevention Association, Foundation for Cross-Connection
Control and Hydraulic Research, or the American Water Works Association.
Backflow prevention assemblies must be tested at least annually and immediately
after installation, relocation or repair. The city of Columbia Falls water
department may require a more frequent testing schedule if it is determined to
be necessary. The city of Columbia Falls water department will maintain records
regarding the inspection, testing, repair, and location of backflow assemblies
on customer premises. No assembly shall be placed back in service unless it is
functioning as required. A report in a form acceptable to the city of Columbia
Fails water department shall be filed with the city of Columbia Falls water
department each time the assembly is tested, relocated or repaired. These
assemblies shall be serviced, over-hauled, or replaced whenever they are found
to be defective and all costs of testing, repair and maintenance shall be borne
by the water user. All repair and maintenance of backflow prevention assemblies
shall be done by a person meeting all state and local requirements. If a water
user has a water service considered critical, i.e. a water service that
can’t be shut off, even for a few moments at any time, the city of
Columbia Falls water department will require either two services to the
facility, each having equal backflow protection determined by the degree of
actual or potential hazard, or the user may install two assemblies in parallel
on the existing service. One assembly can provide water service to the user
while the other is tested and/or repaired.
2. The city of Columbia Falls water department will notify
affected customers by mail when annual testing of an assembly is needed and also
supply users with the necessary forms which must be filled out each time an
assembly is tested or repaired.
3. Upon request, the city of Columbia Falls water department
will provide a list of persons qualified to test backflow prevention
assemblies.
E. Backflow Prevention Assembly Removal. Approval must be
obtained from the city of Columbia Falls water department before a backflow
prevention assembly is removed, relocated, or replaced.
1. Removal. The use of an assembly may be discontinued and
the assembly removed from service upon verification by the city of Columbia
Falls water department that a hazard no longer exists or is not likely to be
created in the future.
2. Relocation. An assembly may be relocated following
confirmation by the city of Columbia Falls water department that the relocation
will continue to provide the required protection and satisfy installation
requirements. A retest will be required following the relocation of the
assembly.
3. Repair. An assembly may be removed for repair provided
the water use is either disconnected until repair is completed and the assembly
is returned to service, or the service connection is equipped with other
backflow protection approved by the city of Columbia Falls water department. A
retest will be required following the repair of the assembly.
4. Replacement. An assembly may be removed and replaced
provided the water use is discontinued until the replacement assembly is
installed. All replacement assemblies must be approved by the city of Columbia
Falls water department and be commensurate with the degree of hazard involved.
The replacement assembly must be tested prior to being put into service. (Ord.
624 § 1(part), 2000)